ES/ESH Troubleshooting

Download ES/ESH Manual

Blower Motor Fails to Run

Blower Motor Fails to Run

  • Is the thermostat calling for heat? Is there 115V at the burner receptacle?
  • Check blower side door for seal. Repair if necessary.
  • Check blower for obstructions. Replace blower if necessary.

No Gas Supply

No Gas Supply

  • Check to see if manual supply valve to heater is open. No manifold pressure indicates valve is closed.
  • Gas pressure downstream of gas control can be measured by connecting a manometer to pressure tap on control.
  • Supply gas pressure can be checked at 1/8" NPT pressure tap in gas supply system.
  • Combination gas control gas valve or the ignition module may be faulty.

Burner Does Not Light

Burner Does Not Light

  • Is spark visible through site glass during ignition trial? If no, further electrical checks by a qualified service person are required.
  • Check to see if gas lines were properly purged of air.
  • Check inlet and outlet gas pressure during ignition period.

Burner Does Not Stay Lit

Burner Does Not Stay Lit

  • Check ground wire continuity.
  • Check insulation on the igniter leads.
  • Measure flame signal current; it should be between 2 to 6 micro amps DC. Minimum 0.8 micro amps
  • Clean flame rod if necessary.
  • Replace module if necessary.