APEX Troubleshooting

Download APEX Manual

Burner Blower / Mother Fails to Run

Burner Blower / Motor Fails to Run

  • Is the thermostat calling for heat? Is there 115V at the burner receptacle?
  • Check blower for obstructions. Replace blower if necessary.
  • Pressure Switch (N.O.) Failed Closed. Replace as necessary.
  • Check High Limit Switch (N.C.) for continuity.

Heat Exchanger Blower Motor Fails to Run

Heat Exchanger Blower Motor Fails to Run

  • Check heat exchanger blower power cord is connected to burner box cable connector.
  • Check blower for obstructions. Replace blower if necessary.

The Ignition Module Fails to Energize the Igniter

The Ignition Module Fails to Energize the Igniter

  • Check air pressure switch performance with a manometer – Compare with switch setting.
  • Ensure the correct size of exhaust and air intake pipes were used per the instruction manual for vent length.
  • Ensure maximum number of elbows or equivalent feet of both pipes was not exceeded.
  • Ensure there are no obstructions in the exhaust and air intake pipes.
  • If the air pressure switch performance test results prove the air pressure switch is working properly, and all other steps are followed, and fault code persist – replace the control.

No Gas Supply

No Gas Supply

  • Check to see if manual supply valve to heater is ON (Open). No manifold pressure indicates valve is closed. Gas pressure downstream of gas control can be measured by connecting a manometer to pressure tap on control. If the valve is closed, neither the gas valve knob on heater gas control is ON.
  • Supply gas pressure can be checked at 1/8" NPT pressure tap in gas supply system.

Burner Does Not Light

Burner Does Not Light

  • Is spark visible through site glass during ignition trial? If no, further electrical checks by a qualified service person are required.
  • Check to see if gas lines were properly purged of air.
  • Check inlet and manifold gas pressure during ignition period.
  • Check for proper orifice and air plate.

Burner Does Not Stay Lit

Burner Does Not Stay Lit

  • Check ground wire continuity.
  • Check insulation on the igniter leads.
  • Measure flame signal current; it should be between 2 to 6 micro amps DC. Minimum 0.8 micro amps
  • Clean flame rod if necessary.
  • Replace module if necessary.